01Note what time it appears and how long the machine has been on
If it always comes up after a certain time of day or after several hours of running, it is thermal accumulation: filters, ambient or airflow. If it comes up shortly after switching on, a stopped fan or a sensor is more likely. This costs nothing to check and steers everything else.
02Check what is accessible from outside
Inlet and outlet grilles clear, with no material stacked in front and no bags or rags. Cabinet filters in plain sight: if they are grey and matted, you already have a cause. Cleaning or replacing filters is done with the machine stopped.
03Listen to the fans
With the machine switched on and from outside, listen for them turning and for any that sounds different from usual. A fan that squeals or hums irregularly is about to stop. If one clearly makes no sound, you know which one to check, but opening the cabinet to verify it is a maintenance job.
04Measure the shop ambient temperature next to the machine
Machines have a permitted ambient temperature range, and in summer many shops exceed it by mid-afternoon. If the ambient next to the machine is above what the manual states, no filter will fix it: the building has to be ventilated or the machine moved away from heat sources.
05Let it cool and see whether it repeats
Switching off and letting it cool clears the alarm, but that is not a diagnosis. What is useful is seeing whether it returns after the same running time. If it is reproducible by running time, the cause is cooling; if it comes straight back with the machine cold, suspect the sensor or the fan itself.
06Fan replacement and internal inspection go to maintenance
Changing a cabinet or control unit fan means working inside the cabinet with the machine locked out, and the correct model has to be fitted with the airflow direction respected. A fan mounted backwards cools worse than none at all. Never work with the cabinet open and energised, and never leave it open to cool things down.