01Stop the machine and do not reset
Every reset attempt with a power fault present can make the damage worse. Leave the machine stopped, do not try to start the spindle, and lock its use out until maintenance has looked at it. This is not over-caution: it is what separates changing a fuse from changing an amplifier.
02Note the drive code and everything visible on screen
The spindle amplifier's alarm number, visible on the control's spindle diagnostic screen, separates a fuse from a phase loss and from a supply failure. Also note whether there are other simultaneous alarms and whether anything else in the shop tripped at the same time.
03Reconstruct the context without opening anything
What the machine was doing, whether there was an impact or a spindle jam, whether anyone noticed a smell, smoke or a sharp bang, whether there was a storm or a power cut, whether coolant has been getting where it should not. All of that steers you between motor, cable and drive.
04Check whether other equipment in the shop is affected
A phase loss on the incoming supply affects more than one machine. If other machines are also showing supply alarms, or something tripped in the main panel, the problem is the installation and not the spindle. This is checked from outside, without opening panels.
05Hand it to electrical maintenance with the machine locked out
Measuring phases, checking fuses, testing the insulation of the spindle motor and its cable, and inspecting the amplifier are jobs done with the machine de-energised, locked out and with proper test equipment. The operator does not open the cabinet, and a fuse is never replaced without first finding out why it opened.
06Do not go back into production until the cause is identified
A fuse changed without explaining why it blew will blow again, and the second time it usually takes something else with it. The machine goes back into production when there is a specific cause corrected and a satisfactory no-load test.